6-9
6.3 Preparing for operation
6 Wiring
6.3.1.6 Example of calculation
Example of calculation6-Verdrahtung_PDP_PSEN_Leitungslänge-Spannungsabfall-Beispiel
A 0.25 mm² sensor cable is used.
Voltage drop per 10 m and per 100 mA: 0.15 V
6.3.1.7 Standard values for a range of cable types
Standard values for a range of cable types6-Verdrahtung_PNOZ ml2p_Leitungslänge-Spannungsabfall-Richtwerte
Guidelines for calculating the voltage drop on various cable types
Cable type Voltage drop per 10 m and per 100
mA
PSS SB BUSCABLE LC 0.1 V
Sensor cable 0.25 mm
2
0.15 V
Sensor cable 0.34 mm
2
0.11 V
Sensor cable 0.5 mm
2
0.07 V